ACS Phone: +43 7228 20088 0

… always

a cable length ahead!

JB-H(St)H Bd

Anwendung

The halogen-free installation cables with improved characteristics in the case of fire are used for the telephone transmission, measurement and control technology. The static screen protects the transmission circuits against outer electrical interferences. A fire propagation is prevented through high oxygen index of the insulation material and produce no corrosive gases in case of fire. Those cables are preferably used for telecommunication indoor installations and in special cases the outdoor installation is permitted under protection against sunlight. These cables are suitable for fixed installation in areas with danger of fire, in dry and damp environments as well as on, in and under plaster.


art. no.
dimensions
colour
outer-Ø
weight
01907001 1 x 2 x 0,8 red 6,9 61
01907002 2 x 2 x 0,8 red 6,7 80
01907003 4 x 2 x 0,8 red 9,9 140
01907015 5 x 2 x 0,8 red 10 144
01907004 6 x 2 x 0,8 red 10,4 170
01907005 10 x 2 x 0,8 red 12,8 250
01907006 16 x 2 x 0,8 red 18 360
01907007 20 x 2 x 0,8 red 19 430
01907008 24 x 2 x 0,8 red 19,3 510
01907009 30 x 2 x 0,8 red 20,1 600
01907010 40 x 2 x 0,8 red 21,2 770
01907011 50 x 2 x 0,8 red 24,9 940
01907012 60 x 2 x 0,8 red 27,2 1120
01907013 80 x 2 x 0,8 red 29,9 1440
01907014 100 x 2 x 0,8 red 35,7 1800
inner conductor bare copper conductor, solid 0,8 mm
core insulation halogen-free compound type HI2
core colour code acc. to DIN VDE 0815
stranding element the cores to quads and the quads are stranded to units, core wrapping with plastic tape
overall shield plastic coated alu-foil with drain wire
outer sheath material halogen-free outer jacket type HM2 to DIN VDE 0207 part 24

adapted to DIN VDE 0815
CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU.

inner conductor bare copper conductor, solid 0,8 mm
core insulation halogen-free compound type HI2
core colour code acc. to DIN VDE 0815
stranding element the cores to quads and the quads are stranded to units, core wrapping with plastic tape
overall shield plastic coated alu-foil with drain wire
outer sheath material halogen-free outer jacket type HM2 to DIN VDE 0207 part 24
rated voltage 300 V
test voltage core/core: Ueff: 800 V
core/screen: 800 V
insulation resistance min. 100 MOhm x km
operating capacity at 800 Hz: max. 120 nF/km
conductor loop resistance at 20°C: max. 73,2 Ohm/km
bending radius fixed 7,5
operation temp. fixed -30°C … +70°C
operation temp. moved -5°C … +50°C
halogenfree adapted to DIN VDE 0815
radiation resistance up to 100x106 cJ/kg (up to 100 Mrad)
corrosivity of combustion gases to IEC 60754-2 or VDE 0482 Teil 267-2-3
fire behavior self-extinguishing and flame retardant
fire test acc. to VDE 0482 part 266-2, BS 4066
part 3, DIN EN 50266-2, IEC 60332-3

Contact

Export

Division Management

Veronika Jautz

phone +43 7228 20088 132
Fax +43 7228 20088 200
jautz.veronika@acs.at