ACS Phone: +43 7228 20088 0

… always

a cable length ahead!

YSLY (blau) eigensicher

Anwendung

For hazardous areas the cables with special marking (blue) (hazard type-i-) used as flexible control and measuring cables to meet the requirements for the installation of electrical apparatus. These installations are not earthed and require a separate power circuit. Those cables are not suitable for underground laying.


art. no.
type
dimensions
colour
outer-Ø
weight
00912010 -OZ 2 x 0,75 blue 6,6 59
00912018 -OZ 2 x 1,0 blue 6,6 62
00912020 -OZ 2 x 1,5 blue 7,4 80
00912011 -OZ 3 x 0,75 blue 7 70
00912021 -OZ 3 x 1,5 blue 8,3 106
00912012 -OZ 4 x 0,75 blue 7,6 84
00912034 -OZ 4 x 1,0 blue 6,6 86
00912022 -OZ 4 x 1,5 blue 9 127
00912031 -OZ 5 x 1,0 blue 7,2 105
00912032 -OZ 7 x 1,0 blue 8,6 141
00912015 -OZ 25 x 0,75 blue 16,6 397
00912028 -OZ 25 x 1,0 blue 17,4 464
inner conductor fine-stranded bare copper acc. DIN VDE 0295 cl. 5 / IEC 60228 cl. 5
core insulation polyvinylchlorid compound (PVC)
core colour code black cores with continuous white numbers printed
stranding element cores stranded in layers with optimal lay-length
outer sheath material PVC to DIN VDE 0281 part. 1

DIN EN 60079-14 and IEC 60079-14 section 12.2.2 (VDE 0165 part 1)
CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU.

inner conductor fine-stranded bare copper acc. DIN VDE 0295 cl. 5 / IEC 60228 cl. 5
core insulation polyvinylchlorid compound (PVC)
core colour code black cores with continuous white numbers printed
stranding element cores stranded in layers with optimal lay-length
outer sheath material PVC to DIN VDE 0281 part. 1
rated voltage Uo/U: 300/500 V
test voltage 3000 V
breakdown voltage min. 6000 V
insulation resistance min. 20 MOhm x km
inductance approx. 0,68 mH/km
operating capacity core/core approx. 120 nF/km
bending radius moved 7,5
bending radius fixed 4
operation temp. fixed -30°C … +80°C
operation temp. moved -5°C … +80°C
radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
fire behavior self-extinguishing and flame retardant acc. to VDE 0482 part 332-1-2,
EN 60332-1-2, IEC 60332-1

Contact

Export

Division Management

Veronika Jautz

phone +43 7228 20088 132
Fax +43 7228 20088 200
jautz.veronika@acs.at