ACS Phone: +43 7228-2008-0

E-AY2Y-O/J

Application

Power cables for energy supply are installed in open air, in underground, in water, indoors, in cable ducts, power stations, for industry and distribution boards as well as in subscriber networks, where mechanical damages are not to be expected.


art. no.
type
dimensions
outer-Ø
weight
power load earth
power load air
01306032 -J 1 x 120 rm 20 525 389 A 302 A
01306024 -O 3 x 240/120 52 3510 364 A 338 A
01306033 -J 3 x 240/120 52 3510 364 A 338 A
01306001 -O 4 x 25 re 25 689 102 A 82 A
01306002 -O 4 x 25 rm 26 700 102 A 82 A
01306034 -J 4 x 25 re 25 689 102 A 82 A
01306040 -J 4 x 25 rm 26 700 102 A 82 A
01306003 -O 4 x 35 sm 24,5 729 123 A 100 A
01306030 -J 4 x 35 sm 24,5 729 123 A 100 A
01306004 -O 4 x 50 se 26,5 900 144 A 119 A
01306005 -O 4 x 50 sm 27 929 144 A 119 A
01306012 -J 4 x 50 se 26,5 900 144 A 119 A
01306031 -J 4 x 50 sm 27 929 144 A 119 A
01306038 -J 4 x 70 sm 32 1341 179 A 152 A
01306006 -O 4 x 95 se 33,5 1573 215 A 186 A
01306007 -O 4 x 95 sm 35 1632 215 A 186 A
01306013 -J 4 x 95 se 33,5 1573 215 A 186 A
01306029 -J 4 x 95 sm 35 1632 215 A 186 A
01306039 -J 4 x 120 sm 41,8 2225 245 A 216 A
01306008 -O 4 x 150 se 42 2320 275 A 246 A
01306009 -O 4 x 150 sm 43 2450 275 A 246 A
01306014 -J 4 x 150 se 40 2320 275 A 246 A
01306022 -J 4 x 150 sm 43 2450 275 A 246 A
01306010 -O 4 x 185 sm 51 3102 313 A 285 A
01306015 -J 4 x 185 sm 51 3102 313 A 285 A
01306011 -O 4 x 240 sm 54,5 3985 364 A 338 A
01306016 -J 4 x 240 sm 54,5 3985 364 A 338 A
inner conductor solid or stranded, alu conductor to DIN VDE 0295 cl. 1 or cl. 2, BS 6360 cl. 1 or cl. 2 and IEC 60228 cl. 1 or cl. 2
core insulation polyvinylchlorid compound (PVC)
core colour code HD 308 S2, 7 cores black with continuous white numbers printed
stranding element multi cores stranded in layers
coat filler sheath or tape
outer sheath material PE - polyethylene compound, black

ÖVE K 23 and K 603
CE = The product is conformed with the EC Low-Voltage Directive 2006/95/EG.

inner conductor solid or stranded, alu conductor to DIN VDE 0295 cl. 1 or cl. 2, BS 6360 cl. 1 or cl. 2 and IEC 60228 cl. 1 or cl. 2
core insulation polyvinylchlorid compound (PVC)
core colour code HD 308 S2, 7 cores black with continuous white numbers printed
stranding element multi cores stranded in layers
coat filler sheath or tape
outer sheath material PE - polyethylene compound, black
rated voltage Uo/U: 0,6/1 kV
test voltage 4000 V
bending radius fixed single core: 15
multi core: 12
operation temp. fixed -20°C … +70°C
operation temp. moved -5°C … +70°C
conductor temp max. +70°C
short circuit temperature up to 300 mm²: max. +160°C
from 400 mm²: max. +140°C
short circuit duration 5 sec.

Contact

Export

Management

Angela Mesarosch

Management Eastern Europe

phone +43 7228 20088-133
Fax +43 7228 20088-200
Mobil +43 664 9624355
mesarosch.angela@acs.at

Prok. Manfred Lederhilger

Export Management

phone +43 7228 20088-342
Fax +43 7228 20088-349
Mobil +43 664 1724858
lederhilger.manfred@acs.at

Division Management

Veronika Jautz

Czech Republic and Slovakia

phone +43 7228 20088 132
Fax +43 7228 20088 200
jautz.veronika@acs.at

Jaroslav Loučka

Czech Republic and Slovakia

Mobil +42 0727 835 409
loucka.jaroslav@acs.at

Angela Mesarosch

Hungary, Romania, Slovenia, Croatia, Serbia, Macedonia

phone +43 7228 20088-133
Fax +43 7228 20088-200
Mobil +43 664 9624355
mesarosch.angela@acs.at

Export Sales Assistant

Monika Bikic MBA

phone +43 7228 20088 140
Fax +43 7228 20088 200
bikic.monika@acs.at

Anita Böröcz

phone +43 7228 20088-130
Fax +43 7228 20088-200
boeroecz.anita@acs.at

Bc. Mariana Horak

phone +43 7228 20088-131
Fax +43 7228 20088-200
horak.mariana@acs.at