L2-Profibus PE, UV-resistant, outdoor installation
Application
This system cable is used to interconnect L2-BUS components. This cable is an economical solution for the cell and field area. For the information exchange between different automation systems as well as for communication with the connected decentralized field units, serial field bus systems are used. The types mentioned here are suitable for outdoor laying (PE sheath).
art. no. |
type |
awg |
dimensions |
colour |
outer-Ø |
weight |
03216002 | Außenverlegung | AWG22/1 | 1 x 2 x 0,64 | black | 8,2 | 68 |
inner conductor | copper, bare (AWG 22/1) |
core insulation | foam-skin-PE |
core colour code | rd, gn |
stranding element | double core |
shielding 1 | polyester foil over stranded bundle, Polyester foil, aluminium-lined |
overall shield | braid shield copper tinned |
outer sheath material | PE |
Profibus acc. to DIN 19245 T3 and EN50170
inner conductor | copper, bare (AWG 22/1) |
core insulation | foam-skin-PE |
core colour code | rd, gn |
stranding element | double core |
shielding 1 | polyester foil over stranded bundle, Polyester foil, aluminium-lined |
overall shield | braid shield copper tinned |
outer sheath material | PE |
test voltage | 1,5 kV |
insulation resistance | min. 1 GOhm x km |
operating capacity | 30 nF/km nom. |
bending radius moved | 15 |
operation temp. fixed | -40°C … +70°C |
fire behavior | self-extinguishing and flame retardant |
Brandlastwerte | 2,26 MJ/m |