ACS Phone: +43 7228-2008-0

NA2XS(F)2Y 6/10 kV, 12/20 kV, 18/30 kV

Application

For laying indoors, in cable ducts, indoors, in ground and water, as well for laying on racks for industrial and switching systems and power stations.


art. no.
type
dimensions
outer-Ø
weight
power load earth
power load air
01507007 6/10 kV 1 x 50 rm/16 26 750 171 A 183 A
01507008 6/10 kV 1 x 70 rm/16 28 850 208 A 228 A
01507005 6/10 kV 1 x 95 rm/16 29 1030 248 A 278 A
01507009 6/10 kV 1 x 120 rm/16 31 1100 283 A 321 A
01507001 6/10 kV 1 x 150 rm/25 32 1300 315 A 364 A
01507010 6/10 kV 1 x 185 rm/25 34 1450 357 A 418 A
01507002 6/10 kV 1 x 240 rm/25 36 1600 413 A 494 A
01507011 6/10 kV 1 x 300 rm/25 38 1850 466 A 568 A
01507012 6/10 kV 1 x 400 rm/35 42 2350 529 A 660 A
01706006 12/20 kV 1 x 50 rm/16 30 830 172 A 185 A
01706007 12/20 kV 1 x 70 rm/16 32 920 210 A 231 A
01706001 12/20 kV 1 x 95 rm/16 33 1050 251 A 280 A
01706004 12/20 kV 1 x 120 rm/16 35 1150 285 A 323 A
01706002 12/20 kV 1 x 150 rm/25 36 1450 319 A 366 A
01706005 12/20 kV 1 x 185 rm/25 38 1550 361 A 420 A
01706003 12/20 kV 1 x 240 rm/25 41 1750 417 A 496 A
01706009 12/20 kV 1 x 300 rm/25 43 2000 471 A 569 A
01706008 12/20 kV 1 x 400 rm/35 46 2400 535 A 660 A
01807004 18/30 kV 1 x 50 rm/16 35 1210 174 A 187 A
01807005 18/30 kV 1 x 70 rm/16 37 1360 213 A 232 A
01807006 18/30 kV 1 x 95 rm/16 38 1480 254 A 282 A
01807007 18/30 kV 1 x 120 rm/16 40 1610 289 A 325 A
01807002 18/30 kV 1 x 150 rm/25 41 1800 322 A 367 A
01807001 18/30 kV 1 x 185 rm/25 43 2400 364 A 421 A
01807003 18/30 kV 1 x 240 rm/25 45 2200 422 A 496 A
01807008 18/30 kV 1 x 300 rm/25 48 2620 476 A 568 A
01807009 18/30 kV 1 x 400 rm/35 51 3080 541 A 659 A
inner conductor stranded aluminum conductor
core insulation conductor screen of semi-conducting compound - XLPE insulation - core screen of semi-conducting compound - semi-conducting swellable tape
shielding 1 copper wire screen
coat separating tape
outer sheath material PE - polyethylene compound, black

DIN VDE 0276 - 620
CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU.

inner conductor stranded aluminum conductor
core insulation conductor screen of semi-conducting compound - XLPE insulation - core screen of semi-conducting compound - semi-conducting swellable tape
shielding 1 copper wire screen
coat separating tape
outer sheath material PE - polyethylene compound, black
rated voltage Uo/U: 6/10 kV, 12/20 kV, 18/30 kV
bending radius fixed 15
operation temp. fixed -20°C … +90°C
operation temp. moved -20°C … +90°C
conductor temp max. +90°C
short circuit temperature max. +250°C
short circuit duration 5 sec.

Contact

Export

Management

Angela Mesarosch

Management Eastern Europe

phone +43 7228 20088-133
Fax +43 7228 20088-200
Mobil +43 664 9624355
mesarosch.angela@acs.at

Prok. Manfred Lederhilger

Export Management

phone +43 7228 20088-342
Fax +43 7228 20088-349
Mobil +43 664 1724858
lederhilger.manfred@acs.at

Division Management

Veronika Jautz

Czech Republic and Slovakia

phone +43 7228 20088 132
Fax +43 7228 20088 200
jautz.veronika@acs.at

Jaroslav Loučka

Czech Republic and Slovakia

Mobil +42 0727 835 409
loucka.jaroslav@acs.at

Angela Mesarosch

Hungary, Romania, Slovenia, Croatia, Serbia, Macedonia

phone +43 7228 20088-133
Fax +43 7228 20088-200
Mobil +43 664 9624355
mesarosch.angela@acs.at

Export Sales Assistant

Monika Bikic MBA

phone +43 7228 20088 140
Fax +43 7228 20088 200
bikic.monika@acs.at

Anita Böröcz

phone +43 7228 20088-130
Fax +43 7228 20088-200
boeroecz.anita@acs.at

Bc. Mariana Horak

phone +43 7228 20088-131
Fax +43 7228 20088-200
horak.mariana@acs.at

Marino Kokalovic

phone +43 7228 20088 134
Fax +43 7228 20088 200
kokalovic.marino@acs.at