ACS Phone: +43 7228-2008-0

N2XS(F)2Y 6/10 kV, 12/20 kV, 18/30 kV

Application

For laying indoors, in cable ducts, indoors, in ground and water, as well for laying on racks for industrial and switching systems and power stations.


art. no.
type
dimensions
outer-Ø
weight
power load earth
power load air
01513005 6/10 kV 1 x 35 rm/16 25 850 187 A 197 A
01513004 6/10 kV 1 x 50 rm/16 26 960 220 A 236 A
01513006 6/10 kV 1 x 70 rm/16 28 1350 268 A 294 A
01513003 6/10 kV 1 x 95 rm/16 29 1620 320 A 358 A
01513007 6/10 kV 1 x 120 rm/16 31 1800 363 A 413 A
01513008 6/10 kV 1 x 150 rm/25 32 2000 405 A 468 A
01513009 6/10 kV 1 x 185 rm/25 34 2400 456 A 535 A
01513010 6/10 kV 1 x 240 rm/25 36 2900 526 A 631 A
01513002 6/10 kV 1 x 300 rm/25 38 3600 591 A 722 A
01513001 6/10 kV 1 x 400 rm/35 42 4600 662 A 827 A
01703004 12/20 kV 1 x 35 rm/16 29 1075 189 A 200 A
01703001 12/20 kV 1 x 50 rm/16 30 1250 222 A 239 A
01703005 12/20 kV 1 x 70 rm/16 32 1700 271 A 297 A
01703002 12/20 kV 1 x 95 rm/16 33 1750 323 A 361 A
01703010 12/20 kV 1 x 120 rm/16 35 1990 367 A 416 A
01703008 12/20 kV 1 x 150 rm/25 36 2460 409 A 470 A
01703009 12/20 kV 1 x 185 rm/25 38 2740 461 A 538 A
01703003 12/20 kV 1 x 240 rm/25 41 3400 532 A 634 A
01703007 12/20 kV 1 x 300 rm/25 43 4400 599 A 724 A
01703006 12/20 kV 1 x 500 rm/25 49 6450 754 A 953 A
01803003 18/30 kV 1 x 50 rm/16 35 1520 225 A 241 A
01803004 18/30 kV 1 x 70 rm/16 37 1790 274 A 299 A
01803001 18/30 kV 1 x 95 rm/16 38 1900 327 A 363 A
01803005 18/30 kV 1 x 120 rm/16 40 2360 371 A 418 A
01803002 18/30 kV 1 x 150 rm/25 41 2460 414 A 472 A
01803006 18/30 kV 1 x 185 rm/25 43 3170 466 A 539 A
01803007 18/30 kV 1 x 240 rm/25 45 3860 539 A 635 A
01803008 18/30 kV 1 x 300 rm/25 48 4490 606 A 725 A
01803009 18/30 kV 1 x 400 rm/35 51 5580 680 A 831 A
01803010 18/30 kV 1 x 500 rm/35 54 6600 765 A 953 A
inner conductor stranded copper conductor
core insulation conductor screen of semi-conducting compound - XLPE insulation - core screen of semi-conducting compound - semi-conducting swellable tape
shielding 1 copper wire screen
coat separating tape
outer sheath material PE - polyethylene compound, black

DIN VDE 0276 - 620
CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU.

inner conductor stranded copper conductor
core insulation conductor screen of semi-conducting compound - XLPE insulation - core screen of semi-conducting compound - semi-conducting swellable tape
shielding 1 copper wire screen
coat separating tape
outer sheath material PE - polyethylene compound, black
rated voltage Uo/U: 6/10 kV, 12/20 kV, 18/30 kV
bending radius fixed 15
operation temp. fixed -20°C … +90°C
operation temp. moved -20°C … +90°C
conductor temp max. +90°C
short circuit temperature max. +250°C
short circuit duration 5 sec.

Contact

Export

Management

Angela Mesarosch

Management Eastern Europe

phone +43 7228 20088-133
Fax +43 7228 20088-200
Mobil +43 664 9624355
mesarosch.angela@acs.at

Prok. Manfred Lederhilger

Export Management

phone +43 7228 20088-342
Fax +43 7228 20088-349
Mobil +43 664 1724858
lederhilger.manfred@acs.at

Division Management

Veronika Jautz

Czech Republic and Slovakia

phone +43 7228 20088 132
Fax +43 7228 20088 200
jautz.veronika@acs.at

Jaroslav Loučka

Czech Republic and Slovakia

Mobil +42 0727 835 409
loucka.jaroslav@acs.at

Angela Mesarosch

Hungary, Romania, Slovenia, Croatia, Serbia, Macedonia

phone +43 7228 20088-133
Fax +43 7228 20088-200
Mobil +43 664 9624355
mesarosch.angela@acs.at

Export Sales Assistant

Bc. Mariana Horak

phone +43 7228 20088-131
Fax +43 7228 20088-200
horak.mariana@acs.at

Philipp Szatmari

phone +43 7228 20088 134
Fax +43 7228 20088 200
szatmari.philipp@acs.at