2YSL(St)CYK

Application

As supply and connecting cable for medium mechanical stresses in fixed installations and forced movements in dry, moist and wet environments and for outdoor applications. Used in the industry , food industry, environmental engineering, packaging industry, toolmaking machinery, handling equipment, for SOMIVERT drivers, they are particularly suitable for use with industrial pumps, ventilators, conveyor belts and air-conditioning installations and similar applications. Installation in hazardous areas.


art. no.
dimensions
colour
outer-Ø
weight
07712015 3 x 50 black 33 2695
07712016 3 x 95 black 41 4105
07712007 4 G 1,5 black 10,6 220
07712003 4 G 2,5 black 12,3 280
07712004 4 G 4 black 14,5 400
07712005 4 G 6 black 16,4 470
07712006 4 G 10 black 20,1 750
07712008 4 G 16 black 23,4 1050
07712009 4 G 25 black 27 1500
07712001 4 G 35 black 30 2050
07712010 4 G 50 black 35 2750
07712011 4 G 70 black 40 3700
07712002 4 G 95 black 42 4600
07712012 4 G 120 black 49 5700
07712013 4 G 150 black 54 7000
07712014 4 G 185 black 59 8380
inner conductor fine-stranded bare copper acc. DIN VDE 0295 cl. 5 / IEC 60228 cl. 5
core insulation polyethylene compound (PE)
core colour code black, brown, grey and green-yellow earth core
stranding element cores stranded in concentric layers
shielding 1 with special aluminium film
overall shield copper braiding, tinned copper, coverage approx. 80 %
outer sheath material special polyvinylchlorid (PVC)

adapted to DIN VDE 0250
CE = The product is conformed with the EC Low-Voltage Directive 2014/35/EU.

inner conductor fine-stranded bare copper acc. DIN VDE 0295 cl. 5 / IEC 60228 cl. 5
core insulation polyethylene compound (PE)
core colour code black, brown, grey and green-yellow earth core
stranding element cores stranded in concentric layers
shielding 1 with special aluminium film
overall shield copper braiding, tinned copper, coverage approx. 80 %
outer sheath material special polyvinylchlorid (PVC)
rated voltage Uo/U: 600/1000 V
test voltage 4000 V
insulation resistance min. 200 MOhm x km
operating peak voltage AC and 3-phase: 700/1200 V
DC: 900/1800 V
operating capacity depending on core profile
Core/Core: 70 up to 250 nF/km
Core/Screen: 110 up to 410 nF/km
bending radius fixed 15
operation temp. fixed -40°C … +70°C
operation temp. moved -5°C … +70°C
radiation resistance up to 80x106 cJ/kg (up to 80 Mrad)
fire behavior self-extinguishing and flame retardant
fire test acc. to VDE 0482-332-1-2,
DIN EN 60332-1-2, IEC 60332-1